4445 S. 74th E. Ave. Tulsa, OK 74145 Phone: 918.627.3188 Fax: 918.627.2676
1415 FM 1960 East Houston, TX 77073 Phone: 281.445.8700 Fax: 281.445.8880
12441 Business Highway 287N Ft. Worth, TX 76179 Phone: 817.230.4249 Fax: 817.350.4537
5116 NW 3rd Street, Oklahoma City, OK 73128 Phone: 405.603.6722 Fax: 405.603.6737
3519 W. Beal City Road, Weidman, MI 48893 Phone: 989.441.1500 Fax: 989.441.1505
9745 E. Hampden Ave., Suite 250 Denver, CO 80231 Phone: 720.833.7032 Fax: 303.344.1525
101 Alexander Avenue Pompton Plains, NJ 07444 Phone: 973.616.4501 Fax: 973.616.4451
7 West End Way Norwell, MA 02061 Phone: 781.261.9688 Fax: 781.261.9679
3180 Industry Drive - Unit "C" North Charleston, SC 29418 Phone: 843.628.1342 Fax: 866.594.3233
3216 Wetmore Ave., Suite 207 Everett, WA 98201 Phone: 425.903.4850 Fax: N/A
206 Eleanor Ct NW, South Prairie, WA 98385 Phone: 425.903.4850 Fax: N/A
6711 NE 58th Ave Vancouver, WA 98661 Phone: 360.694.6242 Fax: 360.737.3766
17902 Georgetown Lane Huntington Beach, CA 92647 Phone: 714.963.6202 Fax: 714.963.6360
14538-121A Avenue Edmonton, AB T5L 4L2 Phone: 780.453.6677 Fax: 780.482.4356
1.888.800.MESA
The Soil Resistivity Kit is designed to conveniently store and carry all the equipment required to calculate the resistivity of soil. The equipment provided is all that is necessary to perform the Wenner Four-Pin and Soil Method, as outlined by the ASTM G 57-78 Standard.
The MC Miller 4-Pin Test Reel has been designed and engineered to be used in conjunction with any one of the MCM's multi-combination family of meters.
The test set-up utilizes the mechanics of the "Four Electrode Method," which was developed by the National Bureau of Standards and is commonly known as the Wenner 4-pin Method. The resultant resistivity is the average resistivity of the soil (electrolyte) to a depth equal to the spacing between adjacent electrodes (soil pins). The maximum depth (pin spacing) of this standard test set has been designed for 20 feet, which is recommended for standard survey.
The Soil Resistivity Reel is made up of four (4) separate, color-coded lead wires of: 5-foot (yellow), 25-foot (orange), 45-foot (red) and 65-foot (black) lengths. Lead wires are harnessed together and mounted on a lightweight handheld reel. Wire ends at the reel are affixed to female banana plug jacks (mounted in the center hub area) while the opposite ends are terminated with Mueller 27-C clips. Two-foot, color-coded, jumper leads with banana plug ends are supplied with soil resistivity reel to facilitate connection between the REEL and your test meter.
All lead wires and jumpers are made of our own No. 16 AWG, 105 strand copper wire with PVC insulation. In addition to our color coding of the wires, all ends are clearly labeled as to their connection point.