Scope: This specification describes single conductor polyvinylchloride (PVC) insulated, 600-volt dual rated type TW/THW. It is intended for ground wire and other general purpose power wiring. It is suitable for lighting and power in residential, commercial and industrial applications with circuits at temperatures from -25C to 75C in wet or dry locations per NEC Article 310 and NFPA Standard 70. This product complies with EU Directive 2002/95/EC known as ROHS.
Applicable Standards:
· ASTM B-1, B-3, and B-8 for copper conductors.
· Underwriters Laboratories (UL / CUL) Standards as follows: 83 (TW/THW) for Thermoplastic Insulated Wire.
Conductors: The single copper conductors shall be solid or stranded annealed or hard uncoated copper per UL83 and ASTM requirements.
Insulation: The conductor shall be insulated with PVC as specified and applied tightly to the conductor in a concentric manner. The minimum at any point shall not be less than 90% of the specified average thickness in compliance with UL 83.
Identification: The wire shall be identified by surface or indent marking indicating the manufacturer, conductor size, voltage rating, UL symbol, and type designation.
Packaging: Standard packages are 500 ft/spool. – 4 per carton, 500 ft. knockout cartons, or 2500 feet/spool. Custom lengths are available.
Testing: The wire shall be continuously spark tested at 7500 Volts DC. Other electrical and mechanical tests shall be in accordance with UL 1581. AWG
Size | Conductor Construction | Insulation (Mils) |
Nominal Overall Diameter (in.) |
Shipping Wgt. (Lbs./Mft.) |
14 | Solid or 7 strands | 30 | 0.13/0.14 | 18/19 |
12 | Solid or 7 strands | 30 | 0.14/0.16 | 28/29 |
10 | Solid or 7 strands | 30 | 0.17/0.18 | 41/42 |
8 | Solid or 7 strands | 45 | 0.22/0.24 | 72/74 |
6 | Solid or 7 strands | 60 | 0.28/0.31 | 105/107 |
4 | 7 or 133 strands | 60 | 0.35/0.39 | 160/167 |
2 | 7 or 133 strands | 60 | 0.41/0.45 | 250/265 |
1 | 19 strands | 80 | 0.54 | 340 |
1/0 | 19 strands | 80 | 0.62 | 410 |