4445 S. 74th E. Ave. Tulsa, OK 74145 Phone: 918.627.3188 Fax: 918.627.2676
1415 FM 1960 East Houston, TX 77073 Phone: 281.445.8700 Fax: 281.445.8880
12441 Business Highway 287N Ft. Worth, TX 76179 Phone: 817.230.4249 Fax: 817.350.4537
5116 NW 3rd Street, Oklahoma City, OK 73128 Phone: 405.603.6722 Fax: 405.603.6737
3519 W. Beal City Road, Weidman, MI 48893 Phone: 989.441.1500 Fax: 989.441.1505
9745 E. Hampden Ave., Suite 250 Denver, CO 80231 Phone: 720.833.7032 Fax: 303.344.1525
101 Alexander Avenue Pompton Plains, NJ 07444 Phone: 973.616.4501 Fax: 973.616.4451
7 West End Way Norwell, MA 02061 Phone: 781.261.9688 Fax: 781.261.9679
3180 Industry Drive - Unit "C" North Charleston, SC 29418 Phone: 843.628.1342 Fax: 866.594.3233
3216 Wetmore Ave., Suite 207 Everett, WA 98201 Phone: 425.903.4850 Fax: N/A
206 Eleanor Ct NW, South Prairie, WA 98385 Phone: 425.903.4850 Fax: N/A
6711 NE 58th Ave Vancouver, WA 98661 Phone: 360.694.6242 Fax: 360.737.3766
17902 Georgetown Lane Huntington Beach, CA 92647 Phone: 714.963.6202 Fax: 714.963.6360
14538-121A Avenue Edmonton, AB T5L 4L2 Phone: 780.453.6677 Fax: 780.482.4356
1.888.800.MESA
Resistance Readings with the Push of a Button. Unique, Error-free Data-logging Option.
· No need to select ranges or adjust dials – the Miller 400D provides a direct read-out of resistance with the push of a button.
· Bluetooth interface allows optional data-logging via a Bluetooth-enabled PC (or PDA)** Rugged, hard plastic case - safe to use on wet ground – IP67 rating for dust and water intrusion.
· Resistance measurement range from 0.01Ω to 10MΩ (auto-ranging). High resolution digital display.
· Resistance measurements are unaffected by any stray interference signals that may be present in the earth during readings, due to the use of narrow band-pass filters centered at 82.2Hz (the unit’s operating frequency).
· Runs on a set of replaceable D-cell alkaline batteries...no need to periodically recharge the unit or to plug it into a power source.
· Performs 10,000 single readings on a fresh set of batteries.
· Integrates with Universal Rectifiers’ Soil Depth Selector/Multi-Pin Cable Harness System (please see Integration with Universal Rectifiers’ Cable Harness)
Software Features and Benefits:
· Errors associated with writing down resistance meter readings and subsequently calculating soil resistivity values based on pin spacings are eliminated using the ProCP Soil Resistivity program in conjunction with the Miller 400D Resistance Meter.
· MC Miller’s ProCP Soil Resistivity application can be run on “off-the-shelf” Pocket PC hardware (Windows Mobile 5.0 or higher) or on a laptop PC. Hardware must be Bluetooth-enabled. Reading locations are represented by user-entered station numbers and readings are automatically position and data/time stamped in cases where a GPS receiver is integrated with the user’s handheld unit.
· Data can be stored for up to 4 electrode (pin) spacings per reading location. Pin spacing values are user-entered in “feet” or in “meters”.
· Resistance data directly acquired from the Miller 400D are converted to soil resistivity values (expressed in ohm.cm units) for each selected pin spacing value. Measured resistance and calculated resistivity values are both stored per reading.
· Survey data are stored in XML files for easy reading by other applications, including ProActive, MC Miller’s Pipeline Integrity Data Management application. ProActive users are able to easily integrate soil resistivity survey data with other “over-the-pipe” survey data for enhanced data analysis. A conversion to XLS file format (Excel Spreadsheet) option is also included.
Storage temperature range (with batteries installed):
-40oC to 50oC (-40oF to 122oF)
Operating temperature range:
-20oC to 54oC (-4oF to 129oF)
Weight:
8.6 lbs (3.9kg)
Width:
12in (30.5cm)
Length:
10.5in (26.7cm)
Height:
5.75in (14.6cm)
Accuracy:
0.01Ω to 1MΩ range
±1.6% ±1LS Display Digit ±0.01Ω
1MΩ to 10MΩ range*
±5% ±1LS Display Digit